Power Supply Insufficient Or Instantaneous Abnormality - Daikin SkyAir RZR-TA Series Service Manual

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811EA

4.48 Power Supply Insufficient or Instantaneous Abnormality

U2
Error Code
Applicable
All outdoor units
Models
Method of Error
The main circuit capacitor voltage of the inverter and the power supply voltage is checked.
Detection
Error Decision
The main circuit capacitor of the tested inverter has abnormal voltage or the power supply voltage
Conditions
is abnormal.
Supposed
 Insufficient power supply
Causes
 Instantaneous power failure
 Defective outdoor fan motor
 Defective outdoor unit PCB
Part 6 Service Diagnosis
Troubleshooting by Error Codes
277

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents