SiUS281811EA
6.7.3 If the Float Switch is OFF with the Thermostat OFF in Cooling
Operation
 When the float switch turns OFF, the drain pump turns ON simultaneously.
 If the float switch remains OFF even after the residual operation of the drain pump has ended,
 The drain pump turns OFF once residual operation has ended, then turns ON again after 5
6.7.4 If the Float Switch Turns OFF and ON Continuously, or the Float Switch
Turns OFF While AF Displayed
Float switch
Thermostat
(running)
Error display
Drain pump
 When the float switch turns OFF, the drain pump turns ON simultaneously.
∗1: If the float switch continues to turn OFF and ON 5 times consecutively, it is judged as a
∗2: The drain pump continues to turn ON/OFF in accordance with the float switch ON/OFF
∗3: While the error code AF is displayed, if the float switch remains OFF even after the
Part 4 Functions and Control
OFF
Float switch
ON
ON
Thermostat
(running)
OFF
ON
Error display
OFF
ON
Drain pump
OFF
the error code A3 is displayed on the remote controller.
seconds.
OFF
ON
1st
2nd
ON
OFF
ON
OFF
ON
OFF
5 min.
5 min.
drain system error and the error code AF is displayed on the remote controller.
even after AF is displayed on the remote controller.
residual operation of the drain pump has ended, the error code A3 will be displayed on
the remote controller.
A3
5 min. 5 sec.
∗1
3rd
4th
5th
AF
5 min.
5 min.
5 min.
Outline of Control (Indoor Unit)
∗2
∗3
A3
5 min.
5 min.
5 sec.
133