Daikin SkyAir RZR-TA Series Service Manual page 253

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811EA
Troubleshooting
Part 6 Service Diagnosis
Diagnosis procedure 1
Infrared presence sensor
error (Error code CE-01)
Is the
connection
of the connector
on infrared presence
sensor PCB (A4P) and
the connector
X2A on A2P
normal?
YES
Is the
connection of the
sensor connector
normal?
YES
Check infrared presence sensor output; refer to
sensor and address data No. 22-25.
Displays
15 by the above
verification method.
YES
Turn off the power and then reconnect.
Displays CE-01
again or 15 for
sensor and
address data.
YES
Troubleshooting by Error Codes
NO
Connect the connector correctly.
NO
Connect the connector correctly.
NO
Normal.
NO
Normal.
Replace the sensor.