Power Transistor Check - Daikin SkyAir RZR-TA Series Service Manual

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811EA
5.4

Power Transistor Check

CHECK 4
Perform the following procedures prior to check.
(1) Power OFF.
(2) Remove all the wiring connected to the PCB where power transistors are mounted on.
[Preparation]
· Multimeter
[Point of Measurement and Judgment Criteria]
· Measure the resistance value using a tester at each point of measurement below, 10 minutes later
after power OFF.
To use analog multimeter:
Measurement in the resistance value mode in the range of multiplying 1 kΩ.
No.
1
2
3
4
5
6
7
8
9
10
11
12
To use digital multimeter:
Measurement is executed in the diode check mode.(
No.
1
2
3
4
5
6
7
8
9
10
11
12
Part 6 Service Diagnosis
Point of
Judgment
Measurement
Criteria
+
P2
U
P2
V
2 ~ 15 kΩ
P2
W
U
P2
V
P2
15 kΩ and
W
P2
above
(including
N3
U
)
N3
V
N3
W
U
N3
V
N3
2 ~ 15 kΩ
W
N3
Point of
Judgment
Measurement
Criteria
+
P2
U
P2
V
1.2 V and
over
P2
W
U
P2
V
P2
W
P2
0.3 ~ 0.7 V
N3
U
N3
V
N3
W
U
N3
V
N3
1.2 V and
over
W
N3
∗ Preparing a multimeter in the analog system is
recommended.
A multimeter in the digital system with diode check
function will be usable.
Remarks
Due to condenser
charge and so on,
resistance
measurement may
require some time.
)
Remarks
Due to condenser
charge and so on,
resistance
measurement may
require some time.
Due to condenser
charge and so on,
resistance
measurement may
require some time.
Check