Daikin SkyAir RZR-TA Series Service Manual page 320

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

Check
7. Locate the 3-circuit connector in the control/end bell. Using an ohmmeter, check the resistance
8. Reassemble motor and control/end bell in reverse of disassembly. Replace blower assembly
Motor Checks
Warning
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing. Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
1. Disconnect power to air handler or modular blower.
2. Disassemble motor as described in steps 2 through 4 above.
3. Locate the 3-circuit harness from the motor. Using an ohmmeter, measure the resistance
4. Measure the resistance between each motor phase winding and the motor shell. Replace the
5. Reassemble motor and control/end bell in reverse of disassembly. Replace blower assembly
314
between each terminal in the connector. If the resistance is 1 MΩ or greater, the control/end bell
is functioning properly. Replace the control/end bell if the resistance is lower than 1 MΩ.
into air handler or modular blower.
NOTE: Motor contains capacitors that can hold a charge for several minutes after disconnecting
power. Wait 5 minutes after removing power to allow capacitors to discharge.
between each motor phase winding. The resistance levels should be equal. Replace the motor
if the resistance levels are unequal, open circuited or short circuited.
motor if any phase winding is short circuited to the motor shell.
into air handler or modular blower.
SiUS281811EA
Part 6 Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents