SiUS281811EA
Note(s)
When the 10 (20)-6 setting is changed to 02, several indoor units are controlled by one remote
controller thermistor, so note that the room temperature might be uneven.
1.5.3 Filter Cleaning Sign
Whether or not to display Filter Cleaning after operation of a certain duration can be selected.
Mode
10 (20)
∗Filter Cleaning is not displayed when an Auto-clean Panel is connected.
1.5.4 Time for Absence Area Detection
(For units with an infrared presence sensor)
By selecting the energy-saving operation mode when absent, the target temperature is shifted to
the energy-saving end by 1°C (1.8°F) (maximum 2°C (3.6°F)) after the state of absence continues
for a certain period of time.
Absent time defined for detection can be selected as follows:
Mode
10 (20)
The set temperature displayed on the remote controller remains the same even if the target
As soon as people are detected while the temperature is shifted, this control will be cancelled
Part 5 Field Settings and Test Operation
Mode No.
First Code No.
10 (20)
6
First Code No. Second Code
No.
01
3
Second Code
First Code No.
No.
No.
01
7
(°F)
87.8
86
84.2
82.4
80.6
78.8
69.8
68
66.2
64.4
62.2
temperature is shifted.
(reset).
Second Code No.
Remote controller thermistor control is not
01
permitted during group control
Remote controller thermistor control is
02
permitted during group control
No.
02
02
State of absence
(°C)
31
30
29
28
27
Cooling (at 28°C (82.4°F))
26
21
Heating (at 20°C (68°F))
20
19
18
17
30 (60)∗
Elapsed time of absence (min.)
∗ The values in parentheses represent the time
when Second code No. is 02.
Field Setting from Remote Controller
: Factory setting
Contents
: Factory setting
Contents
Displayed
Not displayed
: Factory setting
Contents
30 minutes
60 minutes
Human detection
60 (120)∗