4.47 Refrigerant Shortage

U0
Error Code
Applicable
All outdoor units
Models
Method of Error
Refrigerant shortage check is conducted based on the discharge pipe thermistor temperature and
Detection
the low-pressure saturated temperature.
Error Decision
Microcomputer is used to determine and check for system refrigerant shortage.
∗The unit can keep operating but there is an unconfirmed error.
Conditions
Supposed
 Refrigerant shortage or refrigerant clogging (piping error)
Causes
 Defective suction pipe thermistor
 Defective pressure sensor
 Defective outdoor main PCB (A1P)
Part 6 Service Diagnosis
Troubleshooting by Error Codes
275