Discharge Pipe Temperature Protection Control

This discharge pipe temperature protection control is used to protect the compressor internal
temperature against an error or transient increase of discharge pipe temperature.
HTdi: Value of inverter compressor discharge pipe temperature (Tdi) compensated with outdoor air
temperature
Tp: Value of compressor port temperature calculated by Tc, Te, and suction superheated degree.
HTdi > 115˚C (239˚F)
OR
Tp > 135˚C (275˚F)
Compressor upper limit
frequency: 1-step down from
current compressor frequency
HTdi > 115˚C (239˚F)
OR
Tp > 135˚C (275˚F)
HTdi > 130˚C (266˚F)
HTdi > 120˚C (248˚F)
OR
for 90 seconds
or more.
36 Hz Unload
120
Discharge pipe protection
control not limited
&
After 30 seconds
In discharge pipe temp.
protection control
OR
Discharge pipe
temperature standby
HTdi < 100˚C (212˚F)
Tp < 110˚C (230˚F)
HTdi < 110˚C (230˚F)
&
Tp < 125˚C (257˚F)
After 20 seconds
HTdi > 135˚C (275˚F)
HTdi > 120˚C (248˚F) for 10 minutes or more.
When occurring 3 times within 100 minutes,
the error code
Compressor upper limit frequency: 1-step
up from current compressor frequency
is output.
F3