Electrical Data

Compressor and Condenser Motor

Electrical Data
Table 11: Compressor and Condenser Motor Data – 208/230 Volt
Data
Compressor Motor
No.
Phase
RPM
HP, Compressor 1
Amps (RLA), Comp. 1
Amps (LRA), Comp. 1
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
Condenser Motor
No.
Phase
HP
Amps (FLA, each)
Amps (LRA, each)
Note:
*Unit operating voltage range is 187 - 253
Table 12: Compressor and Condenser Motor Data – 460 Volt
Data
Compressor Motor
No.
Phase
RPM
HP, Compressor 1
Amps (RLA), Comp. 1
Amps (LRA), Comp. 1
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
Condenser Motor
No.
Phase
HP
Amps (FLA, each)
Amps (LRA, each)
Note:
*Unit operating voltage range is 414 - 506
24
Electrical Data (208/230 V)*
MPS
MPS
MPS
015B
020B
025B
2
3
3450
7-1/2
10
11-1/2
25
33.3
48.1
164
239
245
7-1/2
7-1/2
11-1/2
25
33.3
48.1
164
239
245
4
6
1
1/3
1.2
4.7
Electrical Data (460 V)*
MPS
MPS
MPS
015B
020B
025B
2
3
3450
7-1/2
10
11-1/2
12.2
17.9
18.6
100
125
125
7-1/2
7-1/2
11-1/2
12.2
14.7
18.6
100
95
125
4
6
1
1/3
0.7
2.4