2.2 GENERAL SETTINGS
Table 2–1: TRIPPING SCHEMES
Number of
Number of
2
Breakers
Trip Circuits
NUM_BKR
NUM_TC
1
1
1
2
2
1
2
2
where: TC1, TC2 = Trip Coils; T1 to T4 = LPS-O Trip Outputs
107: NUM_MON - Trip Outputs To Be Monitored
Trip circuit monitoring can be used to check the integrity of the trip circuit to which the selected trip output is
connected. It does this by sensing the voltage across the trip output as shown in Figure 2–1: TRIP CIRCUIT
MONITOR. If the trip circuit is intact, almost full DC voltage will be detected across the trip output. If the trip cir-
cuit is open for some reason, there will be no voltage (or very little voltage) across the trip output. The monitor-
ing circuit will detect this condition and store an event. It can also can be programmed to close an alarm
contact if so desired.
The trip contacts are also monitored when a trip is initiated by the LPS-O system. If the voltage across the con-
tacts does not drop when the trip is initiated, then it is assumed that the trip circuit is not intact and an alarm is
issued. If the voltage does drop concurrently with the trip initiation, then the trip circuit is considered to have
been activated and no alarm is issued.
Any or all of the outputs (T1 to T4) can be monitored regardless of whether or not they are used in a trip circuit.
The setting format for NUM_MON is abcd , where any position can be a zero (0) or a one (1) as shown in Table
2–2: SETTING FORMAT FOR NUM_MON.
2-
4
Trip Output Assignments
Breaker No. 1
Trip Circuit 1
Trip Circuit 2
TC-1
TC-2
T1
-
T1
T2
T1
-
T1
T2
(+) DC
TRIP OUTPUT
VOLTAGE
TRIP OUTPUT
(FROM LPS-O)
MONITOR
(FROM ALPS)
52
TC
(-) DC
Figure 2–1: TRIP CIRCUIT MONITOR
LPS-O Line Protection System
2 CALCULATION OF SETTINGS
Breaker No. 2
Trip Circuit 1
Trip Circuit 2
TC-1
TC-2
-
-
-
-
T2
-
T3
T4
GE Power Management