GE LPS-O Instruction Manual page 258

Line protection system
Table of Contents

Advertisement

12.1 INTRODUCTION
Table 12–3: ASCII COMMAND LIST
ASCII
Command Description
Command
Mnemonic
EVEnts
Display events
12
TRIP
Open Breaker command;
issues the command to
open breaker; breaker will
be determined by settings
NUM_BRKR and NUM_TC
CLOSe
Close Breaker command;
issues the command to
close breaker; breaker will
be determined by settings
NUM_BRKR and NUM_TC
ENOUT
Enable outputs
DISABle
Disable outputs
outputs
STATUs
Display status of the relay
DATAReset
Clear various data logs
maintained in the relay
DIGTest
Perform Digital Output
tests; the test energizes
the selected output until
END is chosen or another
output is tested
12-
4
(Sheet 3 of 7)
Lowest
Relay Prompt
Level
Password
Needed
VIEW
List of events with date and time. Example:
06/30/98 16:26:29.7562 Host Logoff on MMI
06/30/98 16:24:37.5944 Host Logon OK on Port 2
06/30/98 16:10:45.6505 Recloser in RESET state
06/30/98 16:10:40.0000 Settings File 0 in Use
06/30/98 16:10:40.0000 System booted
Press ENTER to continue, B to go back a screen,
or ESC to quit
CONTROL
Enter Breaker No. (1 / 2 / BOTH)
TRIP BREAKER 1, ! Are you sure? (Y/N)
Breaker open command sent
CONTROL
Enter Breaker No. (1 / 2 / BOTH)
CLOSE BREAKER 1,! Are you sure? (Y/N)
Breaker close command sent
CONTROL
Enable Outputs, Are you sure? (Y/N)
Outputs are disabled or Outputs cannot be
disabled
CONTROL
Disable Outputs, Are you sure? (Y/N)
Outputs are disabled or Outputs cannot be
disabled
VIEW
RELAY STATUS
Refer to the servicing section for status messages
for the LPS-O
Press ENTER to continue
SETTING
To clear FAULT REPORT and OSCILLOGRAPHY
enter F
To clear OST REPORT enter S
To clear EVENT DATA enter E
To reset target LED and clear warn, failure, and
trip messages enter L
To clear BREAKER HEALTH enter B
To quit press ESC
Enter your choice:
MASTER
Turn Protection off (Y/N):
Enter the number of the Digital Output to be tested
(1 to 18)
Enter END to end test
To see list of Digital Outputs enter H
To quit press ESC
Enter your choice: 4
Digital Output #4 is Activated
Turn Protection on? (Y/N):
LPS-O Line Protection Relay
12 ASCII COMMUNICATIONS
User Response
None
1, 2, or BOTH;
Y to trip, N to
cancel
1, 2, or BOTH;
Y to trip, N to
cancel
Y for OK, N to
cancel;
command
Y for OK, N to
cancel;
command
None
Enter letter,
press ENTER
Enter letter;
Enter digit form
1 to 18; enter
letter
GE Power Management

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lpsob35u23ve1n

Table of Contents