GE LPS-O Instruction Manual page 161

Line protection system
Table of Contents

Advertisement

6 FUNCTIONAL TESTS (USER SETTINGS)
I
= [________] A
T
∠ I
= [________]°
1
3. Connect the relay as shown in Figure 5–1: PHASE-TO-PHASE TEST CONNECTIONS on page 5–7 for
the appropriate phases under test. Set the relay to test mode 14 (Any Zone 1 Phase). The LUI displays:
ANY Z1 PHASE ON
4. Set the voltage inputs to the following values:
VA: 67 volts rms ∠0°,
VB: 67 volts rms ∠–120°,
VC: 67 volts rms ∠+120°.
5. Set the fault current phase angle to ∠ I
out of phase with the line to which it is shorted.
6. Set the fault current to I
check that the A1 contact closes when the voltages are within 7% of V
7. Repeat the test for phase BC and CA faults.
1. Protection Settings:
Z1DISTANCE
(101)
Z1PHASE = NO
Z2DISTANCE
(201)
Z2PHASE = YES
Z2PHREACH = [________] Ω
(202)
(204)
Z2TIMER = YES
(205)
Z2P_TIME = 1.0 sec.
Z3DISTANCE
(301)
Z3PHASE = NO
Z4DISTANCE
(401)
Z4PHASE = NO
LINEINFO
(1204) TRSFMRTYPE = NONE
2. Record the following values:
V
= [________] V
NOM 2
I
= [________] A
T
∠ I
= [________]°
2
3. Connect the relay as shown in Figure 5–1: PHASE-TO-PHASE TEST CONNECTIONS on page 5–7 for
the appropriate phases under test. Set the relay to test mode 15 (Any Zone 2 Phase). The LUI displays:
ANY Z2 PHASE ON
GE Power Management
= [________]° lagging. Note that the leading phase angle is 180°
1
= [________] A rms. Simultaneously reduce the voltage of the faulted phases and
T
LPS-O Line Protection System
6.3 ZONE REACH TESTS
.
NOM 1
6.3.5 T12 – ZONE 2 PHASE REACH TEST
6
6-
11