One test may be performed at a time. When a new test is selected, the previous test will be deselected.
Other activities using the [SET], [ACT] or [INF] keys may be performed during the relay test. When the relay
test category is re-selected, the test started earlier will be remembered only if the [END] key has not been
used. If the digital outputs were enabled, the relay will again ask if they should be disabled. If protection was
disabled, the relay will prompt to enable it before proceeding with the tests again.
NOTE: The Disable Output? screen may appear first.
To remove the relay from test mode, the select 1. End Test Mode and press the [ENT] key. The cursor can be
moved to the item in two ways: by using the arrow keys or by entering [1] followed by [ENT] key. If 1. End Test
Mode is selected, the message ON will be removed from the display line of the item under test and the relay
test terminated.
If outputs have been disabled before the relay test, a prompt appears after the selection of 1. End Test Mode
option, as shown below:
If YES is chosen, the outputs are enabled, the status LED may turn GREEN (if disabling outputs or relay test
was the cause to turn it RED), and the ACT command menu is displayed. If NO is chosen, the outputs remain
disabled, the status LED stays RED and the ACT command menu is displayed. If any other key is pressed, an
error message is generated and [CLR] key must be pressed to clear the message.
The available LPS-O tests and their corresponding numbers are:
1: End Test Mode
2: ZONE 1 AB
3: ZONE 1 BC
4: ZONE 1 CA
5: ZONE 2 AB
6: ZONE 2 BC
7: ZONE 2 CA
8: ZONE 3 AB
9: ZONE 3 BC
10: ZONE 3 CA
11: ZONE 4 AB
This command tests the display, keypad, and LEDs. This test does not require a specific privilege level.
GE Power Management
RELAY TEST
Enable outputs?
12: ZONE 4 BC
13: ZONE 4 CA
14: ANY Z1 PHASE
15: ANY Z2 PHASE
16: ANY Z3 PHASE
17: ANY Z4 PHASE
18: IT DETECTOR
19: IB DETECTOR
20: GRD DIR TRIP
21: GRD DIR BLOCK
22: FAULT DETECTOR
8.1.17 KEYPAD/DISPLAY INTERFACE TEST
LUI TEST
1.Display
2.LEDs
3.Keypad
LPS-O Line Protection System
8.1 INTRODUCTION
23: REM OP DETCT
24: OUT OF STEP BLK
25: V1 DETECTOR
26: LINE OVERLOAD
27: INST PHS OVRC
28: INST GND OVRC
29: LINE PICKUP
30: OVER VOLTAGE
31: UNDER VOLTAGE
32:OUT OF STEP TRIP
8
8-
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lpsob35u23ve1n

Table of Contents