en | System menus and screens
Incoming Format Errors
Incoming Retried Messages The total number of messages successfully received from this
Total Outgoing Messages
Outgoing Retried Messages The total number of message retries to this transponder. This
Outgoing Failed Messages
Auto scan
Stress test
Current Troubles
[Not Responding Map]
2019.08 | V2.18.1.6 | DOC
The number of messages received from this transponder where
format error was detected. This field is yellow if 1.5% or more of
the messages had errors. A high level of message errors
indicates a serious communication problem.
transponder that indicated they were retried. This field is yellow
if 1.5% or more of the messages are retried. A high level of
retried messages indicates a serious communication problem.
The total number of messages sent to this transponder from the
Central Console.
field is yellow if 1.5% or more of the messages are retried. A high
level of retried messages indicates a serious communication
problem.
This is total number of messages that could not to be delivered
to this transponder. This field is yellow if there are any failed
messages. Outgoing failed messages cause the Central Console
to display an alert message that communications have failed.
The auto scan function performs the above stress test
proceeding from one transponder to the next after one of each
type of map is requested and received. After the last map type
and before proceeding to the next transponder, a command is
issued to refresh the transponder data so that when an auto
scan proceeds through all transponders, all transponder and
point troubles are updated. Auto scan is terminated by removing
the check in the Auto scan checkbox or by closing the screen
using the [Cancel] button.
This checkbox causes the Central Console to continually request
maps from the transponder. When in this mode, the Central
Console sends a new map request as soon as it receives a map
from the transponder, rotating through the map types. This test
is used when diagnosing communications problems to create
artificially high traffic on the communication link without
interfering with the processing of alarms and tests. The stress
test ceases when the checkbox is cleared, or this screen is
closed by clicking the [Cancel] button.
This window displays all current troubles for this transponder. In
the Current Transponder Status dialog, there is a low battery
and a tamper condition being reported for this transponder. This
window also displays the restoration to a normal condition when
it occurs. When the fault is corrected, clicking the
[Acknowledge] button eliminates any restoration reports.
Conditions, which were not rectified, remain in the window.
To assist in diagnosing problems with the receivers and alert
units associated with a transponder, several commands can be
issued from the Central Console to requesting information from