Digital Outputs [540] - Omron SX-F Instruction Manual

High power direct torque control inverters
Table of Contents

Advertisement

I/Os and Virtual Connections [500]

11-5-4 Digital Outputs [540]

Communication information
Modbus Instance no/
DeviceNet no:
Profibus slot/index
EtherCAT index (hex)
Fieldbus format
Modbus format
AnOut2 Advanced [536]
Same functions and submenus as under AnOut1 Advanced [533].
Communication information
Modbus Instance no/
DeviceNet no:
Profibus slot/index
EtherCAT index (hex)
Submenu with all the settings for the digital outputs.
Digital Out 1 [541]
Sets the function for the digital output 1.
Note The definitions described here are valid for the active output condition.
Default:
Off
On
Run
Stop
0Hz
Acc/Dec
At Process
At Max spd
No Trip
Trip
AutoRst Trip
Limit
Warning
43262
169/166
4cbe
UInt
UInt
536 AnOut2 Advan
Stp
A
43263–43267
43546
43556
169/167–169/171
170/195
170/205
4cbf-4cc3
4dda
4de4
541 DigOut 1
Stp
A
Ready
0
Output is not active and constantly low.
Output is made constantly high, i.e. for checking circuits
1
and trouble shooting.
Running. The VSD output is active = produces current for
2
the motor.
3
The VSD output is not active.
4
The output frequency=0±0.1Hz when in Run condition.
The speed is increasing or decreasing along the acc. ramp
5
dec. ramp.
6
The output = Reference.
7
The frequency is limited by the Maximum Speed.
8
No Trip condition active.
9
A Trip condition is active.
10
Autoreset trip condition active.
11
A Limit condition is active.
12
A Warning condition is active.
Section 11-5
Ready
207