Process and Application Parameters [300]

11-3-3 Start/Stop settings [330]

Submenu with all the functions for acceleration, deceleration, starting, stop-
ping, etc.
Acceleration Time [331]
The acceleration time is defined as the time it takes for the motor to acceler-
ate from 0 rpm to nominal motor speed.
Note If the Acc Time is too short, the motor is accelerated according to the Torque
Limit. The actual Acceleration Time may then be longer than the value set.
Default:
Range:
Communication information
Modbus Instance no/
DeviceNet no:
Profibus slot/index
EtherCAT index (hex)
Fieldbus format
Modbus format
Fig. 68 shows the relationship between nominal motor speed/max speed and
the acceleration time. The same is valid for the deceleration time.
Nominal
Speed
Max
Speed
Fig. 68
Acceleration time and maximum speed
Fig. 69 shows the settings of the acceleration and deceleration times with
respect to the nominal motor speed.
331 Acc Time
Stp
10.0s
A
10.0 s
0–3600 s
43101
169/5
4c1d
Long, 1=0.01 s
EInt
rpm
100% n
MOT
80% n
MOT
(06-F12)
Section 11-3
8s
10s
t
131