3RA61/3RA62 compact starter
5.8 Diagnostics
Signaling contact 3RA62 compact starter (reversing starter)
Table 5- 14
Status of the signaling contacts on the 3RA62 compact starter (reversing starter)
Compact starter
Actuator
status
Switched off
(delivery condition)
Control supply
voltage present with
actuator set to OFF
Ready
Switched on
(direction of rotation
1)
Switched on
(direction of rotation
2)
Overload protection function
Overload tripped
Short-circuit protection function
Short circuit tripped
TRIPPED
Malfunction (e.g. end of service life reached)
Malfunction tripped
TRIPPED
88
Main contacts
Direction of
Direction of
rotation 1
rotation 2
OFF
Open
Open
OFF
Open
Open
READY Open
Open
READY Closed
Open
READY Open
Closed
READY Open
Open
Open
Open
Open
Open
Auxiliary and signaling contacts
Auxiliary contacts
"Overload"
signaling contact
Querying the position
of the main contacts
13/14: Open
95/96: Closed
95/98: Open
43/44: Open
13/14: Open
95/96: Closed
95/98: Open
43/44: Open
13/14: Open
95/96: Closed
95/98: Open
43/44: Open
13/14: Closed
95/96: Closed
95/98: Open
43/44: Open
13/14: Open
95/96: Closed
95/98: Open
43/44: Closed
13/14: Open
95/96: Open
95/98: Closed
43/44: Open
13/14: Open
95/96: Closed
95/98: Open
43/44: Open
13/14: Open
95/96: Closed
95/98: Open
43/44: Open
System Manual, 08/2018, NEB560060102000/RS-AB/007
"Fault"
signaling
contact
77/78: Open
—
—
77/78: Open
—
—
77/78:
Closed
—
—
77/78:
Closed
—
—
77/78:
Closed
—
—
77/78:
Closed
—
—
77/78: Open
—
—
77/78: Open
—
—
SIRIUS 3RA6 compact starter