No.
Display element/operator control
(14)
"Malfunction" mechanical display
(15)
"Control supply voltage" connection
You can find detailed information on the precise device statuses in "Diagnostics
1)
(Page 87)".
SIRIUS 3RA6 compact starter
System Manual, 08/2018, NEB560060102000/RS-AB/007
Marking
Explanation
RLT 0%
No display: Device is OK
•
White display: Malfunctions detected. Device
•
must be replaced.
A1+, A2/B2-, B1+
Please note the polarity when connecting with DC.
Even if the polarity is reversed, the LED "Control
supply voltage present" lights up, but the compact
starter does not switch on.
3RA61/3RA62 compact starter
5.2 Description of the hardware
1)
51