Siemens SIRIUS 3RA6 System Manual page 142

Load feeder compact starter
Hide thumbs Also See for SIRIUS 3RA6:
Table of Contents

Advertisement

3RA64/3RA65 compact starter with IO-Link
6.10 Commissioning
RESET M/A
Select manual or auto reset following an overload trip on the "RESET M/A"
(manual/automatic) selector switch:
● Manual reset: Following overload trip, reset the 3RA64/3RA65 compact starter with IO-
Link manually by:
– sending the control command "Remote reset" via IO-Link.
– pressing the "Reset" button on the operator panel.
– pressing the blue Reset button.
● Auto reset: Following an overload trip, the 3RA64/3RA65 compact starter with IO-Link is
reset automatically after 3 minutes. However, a manual reset as described above can still
be performed if you have selected this setting.
Figure 6-7
For additional information on the manual and auto reset functions, please refer to "Overload
protection function (Page 58)".
142
Setting RESET M/A on the compact starter with IO-Link
SIRIUS 3RA6 compact starter
System Manual, 08/2018, NEB560060102000/RS-AB/007