7.7.3.4

Uninstalling the accessories for the infeed system for 3RA6

Requirements
Hazardous voltage!
Will cause death or serious injury.
Before starting work, disconnect the system and the device from the power supply.
● The compact starters and circuit breakers must have been removed from the infeed
system for 3RA6. For additional information on this topic, please refer to "Removing the
compact starter from an infeed system for 3RA6 (Page 72)".
● Flat-head screwdriver with max. blade width of 3 mm and total max. length of 120 mm for
levering out the link wedges and releasing the PE tap and PE extension connectors.
Removing PE accessories
The PE infeed is mounted on the right or left of the base carrier.
Step
1
2
3
4
SIRIUS 3RA6 compact starter
System Manual, 08/2018, NEB560060102000/RS-AB/007
DANGER
Instructions
Use a screwdriver to lever out the link
wedge.
Push the PE infeed downwards.
Pull the PE extension connector down
and out and then remove the PE infeed
sideways.
Press the clip on the PE tap backwards
and then pull the PE tap down and out
of the infeed or extension module.