Accessories
7.12 AS-i mounting module for 3RA61/3RA62 compact starter
Undervoltage and overvoltage detection
If an undervoltage or overvoltage is detected when an AS-i output bit (D0 or D1) is set, the
compact starter switches off. The compact starter can only be switched on again when the
AUX PWR returns to the normal range of 24 V ± 20% and the AS-i output bit (D0 or D1) has
been reset.
Compact starter not
controlled
Compact starter
controlled
236
Undervoltage detection
takes place via
the AS-i mounting module from approx.
24 V - 20%
the compact starter.
AS-i mounting module is deactivated.
System Manual, 08/2018, NEB560060102000/RS-AB/007
Overvoltage detection
takes place via
the AS-i mounting module from
approx. 24 V + 20%
the AS-i mounting module from
approx. 24 V + 20%
SIRIUS 3RA6 compact starter