Siemens SIRIUS 3RA6 System Manual page 183

Load feeder compact starter
Hide thumbs Also See for SIRIUS 3RA6:
Table of Contents

Advertisement

Removing a spring-loaded infeed with extension module from a standard mounting rail rail
The spring-loaded infeed is mounted on the right or left of a 3-slot or 2-slot extension
module.
Hazardous voltage!
Will cause death or serious injury.
If extension connectors or end covers are missing, direct contact with live parts is possible.
When installing/removing an extension connector or an end cover the system power supply
must be switched off.
Step
1
2
3
4
5
6
SIRIUS 3RA6 compact starter
System Manual, 08/2018, NEB560060102000/RS-AB/007
DANGER
Instructions
Remove the extension connector that
has been used to connect the extension
module to the spring-loaded infeed.
Use a screwdriver to lever out the 2 link
wedges that have been used for the
mechanical connection between the
extension module and the spring-loaded
infeed.
Pull the extension module down until it
can be pulled away from the standard
mounting rail.
Pull the extension module away from
the standard mounting rail and lift it off
the rail's upper edge.
Pull the spring-loaded infeed down until
it can be pulled away from the standard
mounting rail.
Pull the spring-loaded infeed away from
the standard mounting rail and lift it off
the rail's upper edge.
7.7 Infeed system for 3RA6
Image
Accessories
183