Combinations - Siemens SIRIUS 3RA6 System Manual

Load feeder compact starter
Hide thumbs Also See for SIRIUS 3RA6:
Table of Contents

Advertisement

6.3.2

Combinations

IO-Link master and IO-Link device combinations are shown in the following table.
IO-Link master...
...according to IO-Link
communication
specification V1.0
...according to IO-Link
communication
specification V1.1
By selection of IODD V1.0.1, the device can be operated according to IO-Link communication specification V1.0.
1)
Differences between IO-Link communication specifications V1.0 and V1.1
● Usable IO-Link telegram length (not relevant)
● Application-specific name:
– V1.0: 64 bytes max.
– V1.1: 32 bytes max.
● IO-Link device LED:
– V1.0: Green
– V1.1: Green blinking
● Device ID:
– V1.0: 0x00
– V1.1: 0x01
● Parameter server functionality:
– V1.0: not available
– V1.1: available
The 3RA64 and 3RA65 compact starters are designed as an IO-Link device according to IO-
Link communication specification V1.0.
SIRIUS 3RA6 compact starter
System Manual, 08/2018, NEB560060102000/RS-AB/007
IO-Link device...
... according to IO-Link communication
specification V1.0
Operation according to specification V1.0
Operation according to specification V1.0
3RA64/3RA65 compact starter with IO-Link
... according to IO-Link communication
specification V1.1
Operation according to specification V1.0
Operation according to specification V1.1
6.3 Configuring
1)
101

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirius 3ra61Sirius 3ra62Sirius 3ra64Sirius 3ra65