Actuator TRIPPED
The compact starter has shut down through tripping of the circuit breaker mechanism
because a malfunction or short circuit has been detected.
The actual trigger event can be identified by referring to the "RLT 0%" display window.
When the actuator is in the TRIPPED position, the 3RA61 compact starter (direct starter)
and 3RA62 compact starter (reversing starter) can adopt the following statuses:
Table 5- 5
Actuator
TRIPPED
TRIPPED
Note
Turning the actuator manually to the TRIPPED position.
The actuator can also be moved to the TRIPPED position manually. In this case, it is not
possible to say whether a short circuit has occurred or whether the actuator has been moved
to the TRIPPED position manually simply by looking at the display elements. However, if the
actuator has been moved to the TRIPPED position manually, the user will be able to turn it
back from the TRIPPED position to the
possible if a short circuit trip has occurred.
For additional information on eliminating malfunctions, please refer to "Shutdown on
malfunction (Page 62)".
For additional information on eliminating short circuits, please refer to "Short-circuit
protection function (Page 60)".
SIRIUS 3RA6 compact starter
System Manual, 08/2018, NEB560060102000/RS-AB/007
Actuator display elements TRIPPED (3RA61/3RA62 compact starter)
Mech. display
RLT 0%
No display
White display
3RA61/3RA62 compact starter
Compact starter status
Short circuit tripped
Malfunction (e.g. end of service life reached)
READY position straight away. This will not be
5.4 Functions
57