Function block "3-position actuator
heating circuit"
This function block provides 3-position control of the heating circuit. Depending on the
plant type, it acts as follows:
• Weather-compensated, on the mixing valve of a space heating system (plant type 1–x)
• Weather-compensated, on the valve in the primary return of a space heating system
with a district heat connection (plant type 3–x)
• Demand-compensated, on the mixing valve of a main flow (plant type 4–x)
• Demand-compensated, on the valve in the primary return of a main flow with district
heat connection (plant type 6–x)

11.1 Operating lines

Line
Function, parameter
81
Maximum limitation of flow temperature
82
Minimum limitation of flow temperature
83
Maximum rate of flow temperature increase
84
Flow temperature boost mixing valve / heat exchanger
85
Actuator running time
86
P-band of control (Xp)
87
Integral action time of control (Tn)

11.2 Limitations

11.2.1

Flow temperature limitations

The following settings can be made:
• Maximum limitation of the flow temperature. At the limit value, the heating curve runs
horizontally. This means that the flow temperature setpoint cannot exceed the maxi-
mum value
• Minimum limitation of the flow temperature: At the limit value, the heating curve runs
horizontally. This means that the flow temperature setpoint cannot fall below the mini-
mum value (exception: with locking signals)
If the setpoint is limited, the display shows:
= for maximum limitation
= for minimum limitation
Both limitations can be deactivated (setting ---).
Minimum limitation is also active during storage tank charging, depending on the kind of
priority.
With plant types 3–1 and 3-3, where maximum limitation is not active during storage
tank charging.
Basic Documentation RVL471

11 Function block "3-position actuator heating circuit"

Unit
Factory
Range
setting
°C
---
--- / 0...140
°C
---
--- / 0...140
°C
---
--- / 1...600
°C
10
0...50
s
120
30...873
°C
32.0
1...100
s
120
30...873
CE1P2524E