ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance
DLP-557
Page 2 of 3
6. Move to the Mon Type Alarms toggle fields. The following selections are possible:
Critical
Allows notification of all Critical alarms as they occur.
Major
Allows notification of all Major and Critical alarms as they occur.
Minor
Allows notification of all Minor, Major, and Critical alarms as they occur.
Event
Allows notification of all alarms and events as they occur.
Reference:
TAP-101
7. Assign the selections by pressing Enter or Return.
8. Repeat Steps 3 through 7 for each HDSL facility in the chassis.
Note: Pressing CONTROL-C and confirming with Y removes all threshold values and
alarm level information from the database for the group and slot selected.
Stop! You have completed this procedure.
Press CONTROL-A For Assistance, CONTROL-C To Clear All PM Counts
Figure 557-1. HDSL PM Configuration Screen (Typical)
2-184
© 2000, ADC Telecommunications, Inc.
Alarm Troubleshooting
HDSL PERFORMANCE MONITORING CONFIGURATION
Group: 6
Circuit: 1
Circuit ID:
15 MINUTE
===================
MONTYPE
THRESHOLD ALM LEVEL
=======
========= =========
FCP
5
EVENT
CVP
6893
EVENT
ESP
65
EVENT
SESP
10
EVENT
SEFSP
10
EVENT
CVs PER SES: 165
DAILY
===================
THRESHOLD ALM LEVEL
========= =========
480
EVENT
67579
EVENT
648
EVENT
100
EVENT
100
EVENT
6147-B