Control bit/value
LD_SLOT
SET_DQA
SET_DQB
TM_CTRL_DQ
SW_ENABLE
RES_ERROR
Reserved
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Explanations
You specify the meaning of the value in SLOT with this load request:
0000
means: No action, idle
B
0001
means: Period duration in μs
B
0010
means: On delay in μs
B
0100
means: Duty cycle
B
Values not listed are invalid and trigger setting of feedback bit ERR_LD (when MODE_SLOT =
0) or ERR_SLOT_VAL (when MODE_SLOT = 1).
You use this bit to set digital output DQn.A when TM_CTRL_DQ and SET_DQB are set to 0.
You use this bit to set digital output DQn.B when TM_CTRL_DQ and SET_DQA are set to 0.
You enable the technological function of the digital output with this bit.
0 means: SET_DQA and SET_DQB define states of DQn.A and DQn.B
1 means: Output sequence defines the state of DQn.A; DQn.B is always 0.
You activate the software enable with this bit. If you are using the hardware enable, it is com-
bined with the software enable.
0 means: Stop output
1 means: Start output
Use of the HW enable is activated through parameter assignment. The HW enable is controlled
externally using the digital input DIn.0.
You use this bit to reset the following feedback bits when errors are pending:
ERR_24V
ERR_DQA
ERR_DQB
ERR_LD
Reserved bits must be set to 0.
Configuring/address space
4.3 Pulse train mode
75