Control bit/value
SET_DQA
SET_DQB
TM_CTRL_DQ
SW_ENABLE
RES_ERROR
Reserved
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Explanations
You use this bit to set digital output DQn.A when TM_CTRL_DQ and SET_DQB are set to 0.
You use this bit to set digital output DQn.B when TM_CTRL_DQ and SET_DQA are set to 0.
You enable the technological function of the digital output with this bit.
0 means: SET_DQA and SET_DQB define states of DQn.A and DQn.B
1 means: Output sequence defines the state of DQn.A; DQn.B is always 0.
You activate the software enable with this bit. If you are using the hardware enable, it is com-
bined with the software enable.
0 means: Stop output
1 means: Start output
Use of the HW enable is activated through parameter assignment. The HW enable is controlled
externally using the digital input DIn.0.
You use this bit to reset the following feedback bits when errors are pending:
ERR_24V
ERR_DQA
ERR_DQB
ERR_LD
Reserved bits must be set to 0.
Configuring/address space
4.1 Pulse output (single pulse) mode
31