Summary of Contents for Siemens Simatic ET 200SP

  • Page 2 ___________________ Digital output module Preface DQ 16x24VDC/0.5A ST ___________________ Documentation guide (6ES7132-6BH00-0BA0) ___________________ SIMATIC Product overview ___________________ Connecting ET 200SP Digital output module ___________________ DQ 16x24VDC/0.5A ST Parameters/address space (6ES7132-6BH00-0BA0) ___________________ Interrupts/diagnostic alarms Manual ___________________ Technical specifications ___________________ Parameter data record 12/2015 A5E03574420-AC...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
  • Page 5: Table Of Contents

    Table of contents Preface ..............................4 Documentation guide ..........................6 Product overview ............................ 9 Properties ..........................9 Connecting ............................11 Wiring and block diagram ....................... 11 Parameters/address space ........................13 Parameters ..........................13 Declaration of parameters ...................... 15 Address space ........................16 Interrupts/diagnostic alarms ........................
  • Page 6: Documentation Guide

    Documentation guide The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP.
  • Page 7 Documentation guide Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942). "mySupport" With "mySupport", your personal workspace, you make the most of your Industry Online Support.
  • Page 8 With the TIA Selection Tool, you can generate a complete order list from your product selection or product configuration. You can find the TIA Selection Tool on the Internet (http://w3.siemens.com/mcms/topics/en/simatic/tia-selection-tool). Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0) Manual, 12/2015, A5E03574420-AC...
  • Page 9: Product Overview

    Product overview Properties Article number 6ES7132-6BH00-0BA0 (packaging unit: 1 unit) 6ES7132-6BH00-2BA0 (packaging unit: 10 units) View of the module ① ⑦ Module type and name Function class ② ⑧ LED for diagnostics Color coding module type ③ ⑨ 2D matrix code Function and firmware version ④...
  • Page 10 ● Color identification labels ● Reference identification label ● Shield connector See also You can find additional information on the accessories in the system manualET 200SP distributed I/O system (https://support.industry.siemens.com/cs/ww/en/view/91696622). Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0) Manual, 12/2015, A5E03574420-AC...
  • Page 11: Connecting

    1-wire connection. You can find information on wiring the BaseUnit in the system manual Distributed I/O System ET 200SP (http://support.automation.siemens.com/WW/view/en/58649293). Note The load group of the module must begin with a light-colored BaseUnit. Keep this in mind also during the configuration.
  • Page 12 Connecting 3.1 Wiring and block diagram Wiring: 1-wire connection of actuators The following figure shows the block diagram and an example for the terminal assignment of the digital output module DQ 16×24VDC/0.5A ST on the BaseUnit BU type A0 (1-wire connection).
  • Page 13: Parameters/Address Space

    Parameters/address space Parameters Parameters for DQ 16x24VDC/0.5A ST The effective range of the configurable parameters depends on the type of configuration. The following configurations are possible: ● Central operation with an ET 200SP CPU ● Distributed operation on PROFINET IO in an ET 200SP system ●...
  • Page 14 Parameters/address space 4.1 Parameters Parameters Range of values Default Parameter Effective range with configuration reassignment software, e.g. STEP 7 in RUN (TIA Portal) GSD file GSD file PROFINET IO PROFIBUS DP Reaction to CPU STOP • Turn off Channel Module Turn off Keep last value •...
  • Page 15: Declaration Of Parameters

    A potential group ends with the dark-colored BaseUnit, which follows a light-colored BaseUnit or server module in the station configuration. See also You can find additional information in the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0) Manual, 12/2015, A5E03574420-AC...
  • Page 16: Address Space

    Parameters/address space 4.3 Address space Address space The module can be configured differently in STEP 7; see following table. Depending on the configuration, additional/different addresses are assigned in the process image output/input. Configuration options of DQ 16x24VDC/0.5A ST You can configure the module with STEP 7 (TIA Portal) or with a GSD file. If you configure the module by means of a GSD file, the configurations are available under various short designations/module names;...
  • Page 17 Parameters/address space 4.3 Address space Address space The following figure shows the assignment of the address space for the DQ 16×24VDC/0.5A ST with value status (Quality Information (QI)). The addresses for the value status are only available if the value status is enabled. Image 4-1 Address space of DQ 16×24VDC/0.5A ST with value status Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0)
  • Page 18: Interrupts/Diagnostic Alarms

    Interrupts/diagnostic alarms Status and error display LED display The figure below shows the LED displays of the DQ 16x24VDC/0.5A ST. ① DIAG (green/red) ② Channel status (green) ③ PWR (green) Image 5-1 LED display Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0) Manual, 12/2015, A5E03574420-AC...
  • Page 19 Interrupts/diagnostic alarms 5.1 Status and error display Meaning of the LEDs The following tables contain the meaning of the status and error displays. Remedial measures for diagnostic alarms can be found in chapter Diagnostic messages (Page 21). DIAG LED Table 5- 1 DIAG LED fault display DIAG LED Meaning...
  • Page 20: Interrupts

    Interrupts/diagnostic alarms 5.2 Interrupts Interrupts The digital output module DQ 16×24VDC/0.5A ST supports diagnostic interrupts. Diagnostics interrupts The module generates a diagnostic interrupt at the following events: ● Short-circuit ● Wire break ● Parameter assignment error ● Supply voltage missing ●...
  • Page 21: Diagnostic Messages

    Interrupts/diagnostic alarms 5.3 Diagnostic messages Diagnostic messages A diagnostics alarm is generated and the DIAG-LED flashes on the module for each diagnostics event. You can read out the diagnostics alarms, for example, in the diagnostics buffer of the CPU. You can evaluate the error codes with the user program. Note Parallel connection of two outputs For parallel connection of two outputs for redundant control of a load, the channel...
  • Page 22: Technical Specifications

    Technical specifications Technical specifications Technical specifications of the DQ 16×24VDC/0.5A ST 6ES7132-6BH00-0BA0 General information Product type designation ET 200SP, DQ 16x24VDC/0.5A ST, PU 1 Firmware version V1.1 FW update possible • Usable BaseUnits BU type A0 Color code for module-specific color identification CC00 label Product function...
  • Page 23 Technical specifications 6.1 Technical specifications 6ES7132-6BH00-0BA0 Address area Address space per module Address space per module, max. 2 bytes; + 2 bytes for QI information Digital outputs Number of outputs Sinking output Sourcing output Short-circuit protection 0.7 to 1.3 A Response threshold, typ.
  • Page 24 Technical specifications 6.1 Technical specifications 6ES7132-6BH00-0BA0 Cable length Shielded, max. 1000 m Unshielded, max. 600 m Isochronous mode Isochronous mode (application synchronized up to terminal) Interrupts/diagnostics/status information Substitute values can be applied Interrupts Diagnostics interrupt Diagnostics alarms Diagnostics Monitoring of the supply voltage Wire break Yes;...
  • Page 25 Technical specifications 6.1 Technical specifications Safety-related shutdown Note The digital output module DQ 16x24VDC/0.5A ST supports safety-related shutdown in connection with a fail-safe power module F-PM-E 24VDC/8A PPM ST: • SIL according to IEC 61508: 2 • Highest attainable safety class in safety mode, performance level according to EN ISO 13849-1: d Residual current for signal state "0"...
  • Page 26 Derating trend The following figure show the load current derating with horizontal and vertical mounting positions. Image 6-1 Load current for mounting position Dimension drawing See manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/58532597/133300) Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0) Manual, 12/2015, A5E03574420-AC...
  • Page 27: Parameter Data Record

    Parameter data record Parameter assignment and structure of parameter data record The data record of the module has an identical structure, regardless of whether you configure the module with PROFIBUS DP or PROFINET IO. With data record 128, you can reconfigure the module in your user program regardless of your programming.
  • Page 28 Parameter data record A.1 Parameter assignment and structure of parameter data record Structure of data record 128 Note Channel 0 includes the diagnostics enable for the entire module. Image A-1 Structure of data record 128 Header information The figure below shows the structure of the header information. Image A-2 Header information Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0)
  • Page 29 Parameter data record A.1 Parameter assignment and structure of parameter data record Parameters The figure below shows the structure of the parameters for channels 0 to 15. You enable a parameter by setting the corresponding bit to "1". Image A-3 Structure byte x to x+1 for the channels 0 to 15 Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0) Manual, 12/2015, A5E03574420-AC...
  • Page 30 Parameter data record A.1 Parameter assignment and structure of parameter data record Error transmitting the data record The module always checks all values of the data record to be sent. The module applies the values from the data record only when all values have been transmitted without errors. The WRREC instruction for writing data records returns the appropriate error code if there are errors in the STATUS parameter.