Configuring/address space
4.3 Pulse train mode
4.3.1.4

Period duration

You set the period duration in µs in the hardware configuration. The value range is
dependent on whether or not the high-speed output function (Page 67) is being used:
High-speed output
Activated
Deactivated
In addition, you can change the period duration via the control interface by entering a new
value in SLOT as integer (UDINT). In so doing, you use the MODE_SLOT control bit to
choose whether you want to apply a change once or cyclically:
MODE_SLOT = 0
MODE_SLOT = 1
You can find additional information under Handling of the SLOT parameters (Page 139).
4.3.1.5

On delay

You set the On delay from 0 to 85 s with a precision of 1 µs in the hardware configuration.
In addition, you can change the On delay via the control interface by entering a new value in
SLOT as integer (UDINT). In so doing, you use the MODE_SLOT control bit to choose
whether you want to apply a change once or cyclically:
MODE_SLOT = 0
MODE_SLOT = 1
You can find additional information under Handling of the SLOT parameters (Page 139).
66
Value range of the period duration
10 ... 85000000 μs
= 10 μs ... 85 s
100 ... 85000000 μs
= 100 μs ... 85 s
One-time change:
As soon as you write the value 1
value from SLOT is applied once as the period duration and kept until the
next change.
A change via SLOT takes effect at the next output sequence. An active
output sequence is not affected by the change.
Cyclic change:
When you write the value 17
value from SLOT in each case is applied cyclically as the period duration.
A change via SLOT takes effect at the next output sequence. An active
output sequence is not affected by the change.
One-time change:
As soon as you write the value 2
value from SLOT is applied once as the On delay and kept until the next
change.
A change via SLOT takes effect at the next output sequence. An active
output sequence is not affected by the change.
Cyclic change:
When you write the value 18
value from SLOT in each case is applied cyclically as the On delay.
A change via SLOT takes effect at the next output sequence. An active
output sequence is not affected by the change.
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
in the corresponding output byte, the
D
in the corresponding output byte, the current
D
in the corresponding output byte, the
D
in the corresponding output byte, the current
D
Manual, 05/2019, A5E35061186-AB