Power On A Ptx5000 With High Capacity Dc Pdus - Juniper PTX5000 Quick Start Manual

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

Power On a PTX5000 with High Capacity DC PDUs

To power on the DC-powered PTX5000 with High Capacity DC PDUs and High Capacity DC PSMs:
NOTE:
After powering off a power supply, you must wait at least 60 seconds before powering it
on again.
1. Verify that the power distribution units (PDUs) and power supply modules (PSMs) are fully inserted in
the chassis and that the captive screws on the faceplates are tightened.
2. Verify that an external management device is connected to one of the Routing Engine ports on the
Control Board (AUXILIARY or CONSOLE).
NOTE:
The management Ethernet port labeled HOST/ETHERNET on the Control Board is not
available until after the initial software configuration. You can monitor the startup process during
the initial installation using devices connected to the AUXILIARY or CONSOLE ports.
3. Turn on power to the external management device.
4. Switch on the customer-site circuit breakers to provide voltage to the DC power source cables.
5. Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect the strap to
one of the ESD points on the chassis.
6. Switch the power switch on one of the PDUs to the on (|) position.
7. Verify that the green PDU OK LED is lit steadily green, indicating that the inputs are receiving power.
8. Verify that the -1 and -2 LEDs for each installed PSM are lit green. Also check the input 1 OK, input 2
OK, output OK, and fault (
NOTE:
The -1 and -2 LEDs are lit depending on the number of PSMs connected to each PDU.
A minimum of three PSMs are required out of a maximum of eight per PDU. Also, each PSM
has LEDs indicating input and output status.
) LEDs on each PSM.
66

Advertisement

Table of Contents
loading

Table of Contents