PDU 0 status:
State Online
BoostConv OK
Feed Switch 150Amps <<<===
Hours Used 142
Firmware Version (MCU1) 03.04
Figure 44: Ampere Switch
WARNING:
AC power cord might overheat. Setting the ampere switch incorrectly might also cause
the site circuit breaker to trip.
NOTE:
The system software gets the system power configuration from the PDU and displays
it in the output of the show chassis environment pdu command. Depending on the setting, the
system software limits the system configuration (FPCs and PICs) to keep the power demand
within the maximum output power available from the PDU.
NOTE:
In a redundant system with two PDUs, the PDUs share the load. If the ampere switch
setting of one PDU is lower than the other, Junos OS reduces the rating of the other PDU to
the lower value.
12. Repeat the procedure for the other High Capacity Delta AC PDU.
If you set the ampere switch in the wiring compartment incorrectly, the