Figure 43: Connecting Ground and Power to a High Capacity Delta AC PDU
8. Verify that the AC power wiring connections are correct.
9. Close the door to the metal AC wiring compartment, and use a number 2 Phillips (+) screwdriver to
tighten the two captive screws to secure the door to the metal AC wiring compartment.
10. Verify that the AC power cord does not touch or block access to PTX5000 components, and that it
does not drape where people could trip on it.
11. Before you power on the PDU, select the switch setting corresponding to the AC input power cord
that is connected to the PDU.
compartment.
If CBL-PTX-AC-D cable is used, set the switch to 60A.
If CBL2-PTX-100AC-D cable is used, set the switch to 100A.
If CBL2-PTX-150AC-D cable is used, set the switch to 150A.
You can verify the switch setting by using the show chassis environment pdu command. The command
displays the input power rating as shown in the following example:
show chassis environment pdu 0
Figure 44 on page 51
shows an ampere switch, located inside the wiring