3.8 Options
3.8.43

Redundant fan (option M61)

To increase the plant availability, the drive can be fitted with an additional, redundant fan. If a
fan in the drive cabinet fails, this is detected immediately by the electronic monitoring of the fan.
The redundant fan is connected by the drive controller without this causing the drive and, in
turn, the drive system to fail. This prevents production failures or interruptions. The
replacement of the defective fan can be postponed to the next planned stoppage.
3.8.44

Suitability for marine use (option M66)

The option is available on request.
A technical check is required on an order-for-order basis. Mechanical design changes may be
required. A technical LoA is required to check the earliest possible delivery time.
Classification societies
With option M66, the drives comply with the requirements of the following marine classification
societies.
● Lloyds Register (LR)
● American Bureau of Shipping (ABS)
● Büro Veritas (BV)
● Det Norske Veritas Germanischer Lloyd (DNV GL)
● China Classification Society (CCS)
The certification that is required for a certain organization is available on request.
Scope of option M66
Option M66 includes the following:
● Painted surface suitable for marine applications
● Reinforced mechanical cabinet design
● Mechanical interlocking system for the cabinet doors
● IP54 degree of protection
● Anti-condensation heating (option L55)
● The drive can be welded to the structure of the ship
3.8.45
Controlled outgoing circuit for anti-condensation heating 1-phase 120 VAC
(option N37)
This option includes a controlled outgoing feeder for external auxiliaries (1-phase 120 VAC,
60 Hz, 1.0 to 3.8 kW). The circuit breaker setting range is cos φ = 1 (8 A to 32 A).
The option is used, for example to operate anti-condensation heating. The controlled outgoing
feeder is protected by a miniature circuit breaker. The contactor is deactivated by means of an
ON command on the drive. The OFF command energizes the contactor.
54
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020