4.6 Active Line Modules Liquid Cooled
Tightening torques:
1. Firstly, tighten the nuts by hand.
Tightening torque: 0.5 Nm
2. Then tighten the nuts in the specified sequence 1 to 4.
Tightening torque: 10 Nm
For installation, M6 threaded bolts and hexagon nuts/grub screws ISO 7436-M6x40-14 H,
property class 8.8 are recommended.
The coolant connections are located on the lower side of the components. All connection
elements can be accessed using an appropriate tool.
● Thread type of water connections: Pipe thread ISO 228 G ½ B.
4.6.7

Technical data

Table 4- 39
Technical data for an Active Line Module Liquid Cooled
Liquid Cooled
Rated power
Infeed
1)
Rated power S1 duty
Infeed power S6 duty (40 %)
Peak infeed power
Regenerative feedback
Continuous regenerative power
Peak regenerative power
Supply voltages
Line voltage
Line frequency
Electronics power supply
DC link voltage
Overvoltage trip
Undervoltage trip
2)
Input currents
Rated input current:
at AC 400 V
Input current
at AC 380 V / AC 480 V
at AC 400 V; S6 duty (40 %)
at AC 400 V; peak current
DC link currents
Rated DC link current:
for 600 V:
DC link current:
for 600 V DC; S6 duty (40 %)
for 600 V DC; peak current
Current carrying capacity
DC link busbars
24 V DC busbars
220
6SL3135-7TE31-2AA3
kW
120
kW (P
)
120
n
kW (P
)
145
S6
kW (P
)
175
max
kW
120
kW
175
V
3 AC 380 ... 480 ±10 % (- 15 % < 1 min)
ACrms
Hz
47 ... 63
V
24 (20.4 ... 28.8)
DC
V
510 ... 720
DC
V
820 ± 2 %
DC
V
360 ± 2 %
DC
A
182
AC
A
192 / 152
AC
A
220
AC
A
267
AC
A
200
DC
A
244
DC
A
292
DC
A
200
DC
A
20
DC
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8