7.3 Interface description
Motor holding brake connection
To ensure reliable opening of the motor holding brake, it requires a 24 V ± 10% voltage
supply at the motor connection. It must be taken into account that voltage dips can occur
along the supply cable.
● Use a Control Supply Module or a regulated DC power supply, whose setpoint is set to
26 V.
● Use supply cables with a minimum cross-section of 1.5 mm² and a maximum length of
100 m.
Danger of death due to high touch voltages for brake cables
For motor cables with integrated brake cable, when the motor is operated, the motor can
charge the brake cable up to hazardous voltage levels. Coming into contact with the
conductors or the shield of the brake cable can result in death or serious injury.
• Use motor cables with separate, shielded brake cables and connect the shield of the
NOTICE
Premature wear of the motor holding brake when operated outside its permissible voltage
range
Operating the motor holding brake outside its permissible voltage range at the motor
connection will damage the brake.
• Ensure that the motor holding brake is only operated within its permissible voltage
NOTICE
Faulty brake function due to inadmissible wear
Inadmissible wear means that the braking function can no longer be guaranteed.
• Comply with the predefined Emergency Stop characteristics.
• Avoid repeated brief acceleration of the motor against a holding brake that is still closed.
Note
The motor brake must be connected via connector X11 and X12 on Double Motor Modules.
It is not permitted to directly connect the cable BR- to the electronics ground M.
466
WARNING
brake cable at both ends.
range.
Consider the operating times of the brakes and the relays in the drive control and
enable.
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8