Siemens SINAMICS S120 Manual page 208

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules Booksize
4.5 Active Line Modules with cold plate
Cold plate
Power factor
Circuit breaker
(IEC 60947 and UL)
Rated short-circuit-current
SCCR
4)
Max. total cable length
5)
Max. permissible heat sink
temperature
Weight
Derating must be applied due to the transfer of heat to the external heat sink. At a temperature of 40° C at the interface
1)
to the power unit, 80% derating occurs for 6SL3136-7TE28-0AA. and 70 % for 6SL3136-7TE31-2AA.
The specified power ratings apply to the line voltage range from 380 V to 480 V.
2)
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
3)
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
4)
Module in the drive system.
Maximum total cable length = Σ motor cables, line feeder cable from line filter to the Line Module
5)
Note
New systems with 80 kW and 120 kW Active Line Modules should ideally be designed with
120 kW Active Line Modules Liquid Cooled in order to avoid power derating.
208
6SL3136-
21-6AA.
7TE
cos φ
1
See Chapter Overcurrent protection using fuses and circuit breakers
(Page 51)
kA
65
See Chapter Combination options, Line Modules with line reactors and line
filters (Page 135)
° C
70
kg
6.1
23-6AA.
25-5AA.
1
1
65
65
73
83
10.2
13.8
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
25-5AA3 +
28-0AA.
Active
Interface
Module
1
1
65
65
83
75
13.8
20.3
Booksize Power Units
31-2AA.
1
65
80
20.4