External air cooling
Rated power
Total power loss
(including electronics losses, see
Power loss tables (Page 756))
DC link capacitance
Active Line Module
Drive line-up, max.
Power factor
Circuit breaker
(IEC 60947 and UL)
Rated short-circuit current
SCCR
3)
Max. total cable length
4)
Sound pressure level
Cooling air requirement
Max. permissible heat sink tempera-
ture
Weight
The specified power ratings apply to the line voltage range from 380 V to 480 V.
1)
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
2)
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
3)
Module in the drive system.
Maximum total cable length = Σ motor cables, line feeder cable from line filter to the Line Module
4)
Table 4- 23
Technical data for Active Line Modules with external air cooling, part 2
External air cooling
Rated power
Infeed
1)
Rated power S1 duty
Infeed power S6 duty (40 %)
Peak infeed power
Regenerative feedback
Continuous regenerative power
Peak regenerative power
Supply voltages
Line voltage
Line frequency
Electronics power supply
DC link voltage
Overvoltage trip
Undervoltage trip
2)
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
6SL3131-
7TE21-6AA.
kW
16
W
282.8
μF
705
μF
20000
cos φ
1
See Chapter Overcurrent protection using fuses and circuit
breakers (Page 51)
kA
65
See Chapter Combination options, Line Modules with line reac-
tors and line filters (Page 135)
dB(A)
< 60
m
/h
56
3
° C
85
Rated voltage for rated data 3 AC 380 V
kg
8.78
6SL3131-
7TE28-0AA.
kW
80
kW (P
)
80
n
kW (P
)
106
S6
kW (P
)
131
max
kW
80
kW
131
V
3 AC 380 ... 480 ±10 % (- 15 % < 1 min)
ACrms
Hz
47 ... 63 Hz
V
24 (20.4 ... 28.8)
DC
V
510 ... 720
DC
V
820 ± 2 %
DC
V
360 ± 2 %
DC
4.4 Active Line Modules with external air cooling
7TE23-6AA.
7TE25-5AA.
36
55
666
945.6
1410
1880
20000
20000
1
1
65
65
< 65
< 60
112
160
90
88
13.77
18.5
7TE31-2AA.
120
120
145
175
120
175
Line Modules Booksize
7TE25-5AA3 +
Active Inter-
face Module
55
945.6
1880
20000
1
65
< 60
160
88
18.5
191