Table 6- 33
X1 motor connection and X11 brake connection for Single Motor Modules 45 A to 200 A
For ring cable lugs without insulation (Page 732)
1)
The circuit for protecting the brake against overvoltage is integrated in the Motor Module and does not need to be in-
2)
stalled externally.
Motor holding brake connection
To ensure reliable opening of the motor holding brake, it requires a 24 V ± 10% voltage
supply at the motor connection. It must be taken into account that voltage dips can occur
along the supply cable.
● Use a Control Supply Module or a regulated DC power supply, whose setpoint is set to
26 V.
● Use supply cables with a minimum cross-section of 1.5 mm² and a maximum length of
100 m.
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Terminal
U2
V2
W2
PE connection
+ (BR+)
- (BR-)
6.4 Motor Modules with cold plate
Technical data
45 ... 60 A:
Threaded bolts M6 / 6 Nm
85 A:
Threaded bolts M8 / 13 Nm
132 ... 200 A:
Threaded bolts M8 / 13 Nm
45 ... 60 A:
Threaded bolts for motor cables: M6 / 6 Nm
Threaded hole for PE: M6 / 6 Nm
85 A:
Threaded bolts for motor cables: M8 / 13 Nm
Threaded hole for PE: M6 / 6 Nm
132 ... 200 A:
Threaded bolts for motor cables: M8 / 13 Nm
Threaded hole for PE: M8 / 13 Nm
X11 brake connector
:
2)
Supply voltage: 24 V DC ±10 %
Max. load current: 2 A
Minimum load current: 0.1 A
Type: Spring-loaded terminal 2 (Page 730)
The brake connector is part of the prefabricated cable.
Motor Modules Booksize
1)
1)
1)
1)
1)
1)
1)
1)
1)