Line Modules Booksize
4.5 Active Line Modules with cold plate
4.5.6

Mounting

Please note the following before mounting an Active Line Module with cold plate on a
customer-specific heat sink:
● Check the surface of the heat sink to ensure that it is not damaged.
● To improve heat transfer, a heat-conducting medium must be used. Special spherical-
indented heat-conducting foil must be used for this purpose. Every component with cold
plate is supplied with heat-conducting foil cut to the right size. The position of the heat
conducting foil should be carefully taken into account (see Fig. "Mounting an Active Line
Module with cold plate on an external heat sink").
Note
Use heat conducting foil
• Also replace the heat-conducting foil when replacing a component.
• Only use heat-conducting foil released or supplied by Siemens.
Table 4- 32
Heat-conducting foil, 100 mm
Heat-conducting foil, 150 mm
Heat-conducting foil, 200 mm
Heat-conducting foil, 300 mm
Note
To mount the components, M6 threaded bolts and hexagon nuts/grub screws ISO 7436-
M6x40-14 H, property class 8.8 are recommended.
204
Overview of heat-conducting foils
Article No.
6SL3162-6FD00-0AA0
6SL3162-6FF00-0AA0
6SL3162-6FH00-0AA0
6SL3162-6FM00-0AA0
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8