Siemens SINAMICS S120 Manual page 306

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules Booksize
4.10 Smart Line Modules with external air cooling
Figure 4-84
Table 4- 84
Dimensions of openings to mount Smart Line Modules with external air cooling
Module width
50 mm
100 mm
150 mm
200 mm
306
Opening to mount Smart Line Modules 50 mm to 200 mm with external air cooling, all
data in mm and (inches)
B in mm (inch)
41.5
(1.63
)
+0.3
+0.012
89.5
(3.52
)
+0.3
+0.012
133
(5.24
)
+0.3
+0.012
173
(6.81
)
+0.3
+0.012
b1 in mm (inch)
20.75
(0.82
)
+0.15
+0.006
19.75
(0.78
)
+0.15
+0.006
16.5
(0.65
)
+0.15
+0.006
11.5
(0.45
)
+0.15
+0.006
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
b2 in mm (inch)
--
50
(1.97
)
±0.15
±0.006
100
(3.94
)
±0.15
±0.006
150
(5.91
)
±0.15
±0.006
Booksize Power Units