Rated input currents
at AC 380 V
at AC 480 V / AC 528 V
at 480 V; S6 duty (40 %)
Peak current
at AC 400 V / AC 480 V)
DC link currents
Rated DC link current:
for 600 V
DC link current:
for 540 V
for 600 V DC; S6 duty (40 %)
for 600 V DC; peak current
Current carrying capacity
DC link busbars
Reinforced DC link busbars
24 V DC busbars
Electronics current drawn
at 24 V DC
Total power loss
(including electronics losses, see Power
loss tables (Page 756))
DC link capacitance
Basic Line Module
Drive line-up, max.
Power factor
3)
Circuit breaker
(IEC 60947 and UL)
Rated short-circuit current
SCCR
4)
Max. total cable length
5)
Max. permissible heat sink temperature
Weight
The specified power ratings apply to the line voltage range from 380 V to 480 V.
1)
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
2)
Only the fundamental component
3)
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
4)
Module in the drive system.
Maximum total cable length = Σ motor cables, line feeder cable from line filter to the Line Module
5)
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
6SL3136-
1TE22-0AA0
A
34.5
AC
A
31 / 29
AC
A
38
AC
A
113 / 91
AC
A
33.5
DC
A
37
DC
A
43
DC
A
100
DC
A
100
ACrms
A
150
ACrms
A
20
ACrms
A
0.9
DC
W
141.6
μF
940
μF
20000
cos φ
Approx. 0.98
See Chapter Overcurrent protection using fuses and circuit
breakers (Page 51)
kA
65
See Chapter Combination options, Line Modules with line
reactors and line filters (Page 135)
° C
70
kg
6.4
Line Modules Booksize
4.8 Basic Line Modules with cold plate
1TE24-0AA0
1TE31-0AA0
69
172
62 / 58
154 / 145
78
193
208 / 172
265 / 252
67
167
48
185
87
217
200
292
200
200
--
--
20
20
1.1
1.6
276.4
618.4
1880
4100
20000
20000
65
65
70
70
10.9
16.4
259

Hide quick links: