Process channel

The process channel functions with the bytes I/O8 through I/O23. The parallel interface used in the
regular R1000 is simulated via are the process channel which makes the direct program selection
possible.
As a new function the inputs read by the R1000 for program selection are mirrored onto the
available outputs of the process channel. It is therefore possible to check the function of the R1000
via the PLC.
Layout of the process channel:
Inputs
Byte
I8
I9
I10
I11
I12
I13
I14
I15
I16
I17
I18
I19
I20
I21
I22
I23
Outputs
Byte
O8
O9
O10
O11
O12
O13
O14
O15
O16
O17
O18
O19
O20
O21
O22
O23
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Detector R1000 series UDK20
with integrated fieldbus interface
Description
Control (previously menu = 0)
Program selection 1 - 255 (previously menu = 1)
free
free
Control sensor 1
free
free
Control sensor 2
free
free
free
free
free
free
free
free
Description
Control signals (0-sheet, 1-sheet, 2-sheet)
Mirroring I9
Sensor selection I10 and measuring value, thickness S1
Measuring value, thickness S1
Control signal sensor 1
Measuring value, thickness sensor 1
Measuring value, thickness sensor 1
Control signal sensor 2
Measuring value, thickness sensor 2
Measuring value, thickness sensor 2
free
free
free
free
free
free
Manual
Communication with the PLC