Example On How To Connect A Wye Connected Three-Phase Ct Set To The Ied - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 4
Analog inputs
4.2.2.5

Example on how to connect a wye connected three-phase CT set to the IED

Figure
25
gives also an overview of the actions which are needed to make this measurement available to the
built-in protection and control functions within the IED as well.
A
B
CT 600/5
Star Connected
Protected Object
ANSI13000002 V2 EN-US
Figure 25: Wye connected three-phase CT set with wye point towards the protected object
74
It is recommended to:
use 1A rated CT input into the IED in order to connect CTs with 1A and 2A
secondary rating
use 5A rated CT input into the IED in order to connect CTs with 5A and 10A
secondary rating
gives an example about the wiring of a wye connected three-phase CT set to the IED. It
For correct terminal designations, see the connection diagrams valid for the
delivered IED.
C
I_A
I_B
I_C
IED
1
2
3
1MRK 511 358-UUS A
SEMOD55055-352 v9
4
SMAI_20
ANSI3000002-2-en.vsd
Application manual