ABB Relion 670 Series Applications Manual page 433

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
100 MVA
100 MVA
15.65kV
ANSI09000041 V1 EN-US
Figure 202: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 202, it is necessary to do
the following:
1.
Set correctly all CT and VT data and phase angle reference channel
"") using PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to the generator CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the following
table:
Table 43: General settings parameters for the Measurement function
Setting
Operation
PowAmpFact
PowAngComp
Mode
Table continues on next page
Application manual
230kV Busbar
300/5
15/0.12kV
V
V
,
AB ,
P
Q
G
4000/5
Short description
Operation Off/On
Amplitude factor to scale
power calculations
Angle compensation for phase
shift between measured I & V
Selection of measured current
and voltage
IED
BC
ANSI09000041-1-en.vsd
Selected
Comment
value
On
Function must be
1.000
Typically no scaling is required
0.0
Typically no angle compensation is required. As
well here required direction of P & Q measurement
is towards protected object (as per IED internal
default direction)
Arone
Generator VTs are connected between phases (V-
connected)
Section 16
Monitoring
PhaseAngleRef (see section