ABB Relion 670 Series Applications Manual page 297

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
Control operation can be performed from the local IED HMI. If the administrator has defined users
with the IED Users tool in PCM600, then the local/remote switch is under authority control. If not,
the default (factory) user is the SuperUser that can perform control operations from the local IED
HMI without LogOn. The default position of the local/remote switch is on remote.
QCBAY
ANSI05000116 V1 EN-US
Figure 118: Signal flow between apparatus control function blocks
Accepted originator categories for PSTO
If the requested command is accepted by the authority, the value will change. Otherwise the
attribute
during a command, then the command is aborted.
The accepted originator categories for each PSTO value are shown in
Table 28: Accepted originator categories for each PSTO
Permitted Source To Operate
0 = Off
1 = Local
2 = Remote
3 = Faulty
4 = Not in use
Table continues on next page
Application manual
SCSWI
SCILO
SCSWI
SCILO
blocked-by-switching-hierarchy is set in the cause signal. If the PSTO value is changed
IEC 61850
SXCBR
SXCBR
SXCBR
SXSWI
Originator (orCat)
4,5,6
1,4,5,6
2,3,4,5,6
4,5,6
4,5,6
189
152
989
en05000116_ansi.vsd
Table 28
Section 13
Control
291