DirModeSelx : The directional mode of step x. Possible settings are off/nondirectional/forward/
reverse.
Characteristx : Selection of time characteristic for step x . Definite time delay and different types of
inverse time characteristics are available.
Table 18:
Curve name
ANSI Extremely Inverse
ANSI Very Inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI/IEEE Definite time
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
IEC Normal Inverse
IEC Very Inverse
IEC Inverse
IEC Extremely Inverse
IEC Short Time Inverse
IEC Long Time Inverse
IEC Definite Time
User Programmable
ASEA RI
RXIDG (logarithmic)
The different characteristics are described in the Technical Reference Manual (TRM).
Pickupx : Operation negative sequence current level for step x given in % of IBase .
Application manual
When inverse time overcurrent characteristic is selected, the trip time of the stage
will be the sum of the inverse time delay and the set definite time delay. Thus, if
only the inverse time delay is required, it is important to set the definite time delay
for that stage to zero.
x means step 1, 2, 3 and 4.
Inverse time characteristics
Section 7
Current protection
GUID-F7AA2194-4D1C-4475-8853-C7D064912614 v4