1MRK 511 358-UUS A
16.5.1
Identification
Function description
Event function
16.5.2
Application
When using a Substation Automation system with LON or SPA communication, time-tagged
events can be sent at change or cyclically from the IED to the station level. These events are
created from any available signal in the IED that is connected to the Event function (EVENT). The
event function block is used for remote communication.
Analog and double indication values are also transferred through EVENT function.
16.5.3
Setting guidelines
The parameters for the Event (EVENT) function are set via the local HMI or PCM600.
EventMask (Ch_1 - 16)
The inputs can be set individually as:
NoEvents
•
OnSet , at pick-up of the signal
•
•
OnReset , at drop-out of the signal
OnChange , at both pick-up and drop-out of the signal
•
AutoDetect
•
LONChannelMask or SPAChannelMask
Definition of which part of the event function block that shall generate events:
Disabled
•
Channel 1-8
•
Channel 9-16
•
•
Channel 1-16
MinRepIntVal (1 - 16)
A time interval between cyclic events can be set individually for each input channel. This can be set
between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that is, no cyclic
communication.
Application manual
IEC 61850
identification
EVENT
It is important to set the time interval for cyclic events in an optimized way to
minimize the load on the station bus.
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
S00946 V1 EN-US
Section 16
Monitoring
SEMOD167950-2 v2
M12805-6 v9
IP14841-1 v1
M12811-3 v2
M12811-5 v2
M12811-15 v2
M12811-29 v3
M12811-34 v1
433