Section 13
Control
•
Disabled, sets all outputs to 0, independent of the values sent from the station level, that is,
the operator station or remote-control gateway.
•
Steady, sets the outputs to a steady signal 0 or 1, depending on the values sent from the
station level.
•
Pulse, gives a pulse with 100 ms duration, if a value sent from the station level is changed
from 0 to 1. That means the configured logic connected to the command function block may
not have a cycle time longer than the cycle time for the command function block.