ABB Relion 670 Series Applications Manual page 432

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 16
Monitoring
Table 42: General settings parameters for the Measurement function
Setting
Operation
PowAmpFact
PowAngComp
Mode
k
VGenZeroDb
IGenZeroDb
VBase (set in
Global base)
IBase (set in
Global base)
Measurement function application for a generator
Single line diagram for this application is given in figure 202.
426
Short description
Disabled / Enabled
Operation
Magnitude factor to scale
power calculations
Angle compensation for phase
shift between measured I & V
Selection of measured current
and voltage
Low pass filter coefficient for
power measurement, V and I
Zero point clamping in % of
Vbase
Zero point clamping in % of
Ibase
Base setting for voltage level
in kV
Base setting for current level
in A
Selected
Comment
value
Enabled
Function must be
1.000
Typically no scaling is required
180.0
Typically no angle compensation is required.
However here the required direction of P & Q
measurement is towards busbar (Not per IED
internal default direction). Therefore angle
compensation have to be used in order to get
measurements in aliment with the required
direction.
L1L2
Only UL1L2 phase-to-phase voltage is available
0.00
Typically no additional filtering is required
25
Set minimum voltage level to 25%
3
Set minimum current level to 3%
35.00
Set LV side rated phase-to-phase voltage
495
Set transformer LV winding rated current
1MRK 511 358-UUS A
Enabled
SEMOD54481-110 v7
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents